eSENSE is an extremely cost-optimised sensor solution. By controlling the ventilation based on actual demand, it helps you decrease energy consumption but still maintain a healthy indoor climate in both residential and commercial buildings.
Specification
Measured gas: Carbon dioxide (CO2)
Operating Principle: Non-dispersive infrared (NDIR)
Measurement range 0─2000ppm
OUT1: 0─10V for 0─2000ppm ±2% of reading ±20mV
OUT2: 2─10V for 0─2000ppm ±2% of reading ±20mV
Accuracy: ±30ppm ±3% of reading
Dimensions: (H x W x D) 100 x 80 x 28mm
Life Expectancy >15years Operation temperature range 0─50°C
Operation humidity range 0─95%RH (non-condensing)
Power supply 24VAC/DC
Power consumption <1W average Communication UART
Display: No